The 100-240V mains model of the N1050 is built for ramp and soak applications, with 5 programs of 4 segments each, added USB functionality, and a 50mA pulse output that can drive up to 4 standard Solid State Relays — well suited to ovens and kilns running multiple ramp and soak stages, autoclaves, machinery and OEM builds, general process equipment, heat treatment, and metal processing. It also offers improved thermocouple support including Type S, providing greater flexibility for high temperatures and backwards compatibility with existing probes.
N1050 is an advanced high performance PID temperature controller featuring a vivid LCD display in a modern design package. It combines the proven robustness of NOVUS PID algorithm with a large and bright easy-to-read multicolor 11-segment LCD display with alphanumeric mnemonics and crystal clear status signaling.
Besides the PID auto-tuning capability, N1050 outputs PWM control mode through pulse or relay. It also features 5 ramp-and-soak profile programs, soft start output and timer function which complement the advanced features of the controller. With password protection, all parameters are configurable by the display menu, via USB port or optional RS485 Modbus interface.
Easy to install and maintain due to its detachable connector, N1050 offers the lowest power consumption in the market. Housed in anti-flame material, it has a 48x48 mm (DIN 1/16) format and low profile front panel. Suitable for hostile environments, it complies with standard EMC regulations, providing robustness and reliability including untapped temperature applications.
✅ 3 Year Manufacturer Warranty — backed by our UK-based technical support
Novus N1050-PR Datasheet Download
Novus N1050-PR Manual Download
Sample Configuration Files For QuickTune (.qtc)
Sample Configuration File PT100 Download
Sample Configuration File Type K Download
Technical Details
SIZE: 48 x 48 x 80 mm (1/16 DIN)
PANEL CUTOUT: 46 x 46 mm (+0.5 -0.0 mm)
SUPPLY: 100 to 240 Vac (±10%), 50/60 Hz / 48 to 240 Vdc (±10%)
INPUT: Thermocouples J, K, T, S and Pt100
OUT1: Voltage pulse, 5 V / 50 mA
OUT2: Relay SPST, 1.5 A / 240 Vac / 30 Vdc
Frequently Asked Questions
How does this differ from the N1030T-PR?
The N1050 steps up to a full ramp-and-soak controller — 5 programs of 4 segments each — plus USB configuration and Type S thermocouple support, versus the N1030T's simpler dual-timer function.
What's the difference between this and the N1050-PR-24V?
Only the supply voltage — this is the 100-240V mains model; the -24V version runs from 12-24V for control-panel or off-grid installations. Ramp & soak programming and outputs are identical.
Can I add RS485 Modbus communication or extra relay outputs?
Yes — for remote/SCADA integration and two additional relay outputs, see the N1050-PRRR-485, which adds an RS485 interface and steps this base pulse+relay pair up to a pulse plus three relay outputs.
Industry Applications
- Heat Treatment & Metal Processing — multi-segment ramp & soak profiles for precise thermal cycles.
- Autoclaves — programmable soak stages support sterilisation/curing cycles with multiple hold points.
- Ovens & Kilns — up to 5 stored programs for repeatable multi-stage firing schedules.