Novus TxIsoLoop-2 - Loop Powered Splitter/Isolator (2CH, 4-20mA)
Novus TxIsoLoop-2 - Loop Powered Splitter/Isolator (2CH, 4-20mA)
Novus TxIsoLoop-2 - Loop Powered Splitter/Isolator (2CH, 4-20mA)

Novus TxIsoLoop-2 - Loop Powered Splitter/Isolator (2CH, 4-20mA)

Vendor
Novus
Regular price
£102.00 (Exc. VAT)
Sale price
£102.00 (Exc. VAT)
Regular price
£120.00 (Exc. VAT)
Sold out
Unit price
per 
Shipping calculated at checkout.

MPN: 8813020200

TxIsoLoop-2 can be used to split a single 4-20mA signal into two separate output channels — simple wiring for fast installation, output powered from the input loop, high accuracy, galvanic isolation, and high reliability. It's popular for PLC applications such as hardware upgrades and asset replacement where two control systems need to read the same 4-20mA input, allowing simple and cost-effective signal splitting.

When duplicating one input signal into two outputs, an external 24VDC power supply is required at terminals 3 and 7.

It can also function as two independent loop isolators. With the wiring configuration below, no external power is required.

TxIsoLoop-1 and TxIsoLoop-2 simplify your application and avoid undesirable ground loops by providing single and dual loop galvanic isolation. The 0/4-20mA input is measured and an identical isolated signal is reproduced at the output.

Recommended for electrical grids where the electric potential difference is a major risk, the TxIsoLoop galvanic isolator works on up to 2 isolated channels and eliminates ground loops, which ensures accuracy and signal safety. This accessory, indispensable for industrial environments, operates with a response time of only 2ms.

3 Year Manufacturer Warranty — backed by our UK-based technical support

Novus TxIsoLoop Datasheet Download

Novus TxIsoLoop Manual Download

Technical Details

Maximum input voltage: 32 Vdc. Voltage drop: <3 Vdc

Output signal: 0(4) to 20mA. Max load: 1450Ω

Accuracy: 0.2% FS @ 0-60°C / RL=250Ω; 0.3% FS @ -20-75°C / RL=250Ω

Operating current: >0.1mA. Overload: <40mA; <32Vdc

Response time: 2ms @ RL=250Ω

Isolation: 3000Vac / 10s; 240Vac continuous. EMC: EN 61326-1

Ambient temperature range: -20 to +75°C. Humidity: 20-90% RH. Protection: IP40

Wire gauge for connections: 0.14 to 1.5mm². Recommended torque: 0.8Nm. Terminal blocks injected in Polyamide

Dimensions: 18mm wide, 72mm deep when DIN rail mounted

Frequently Asked Questions

Does the device require external power?
To split one 4-20mA signal into two outputs, 24VDC is required. In standard isolation mode, the device does not require external power.

Are there any DIP switches to set?
No — this device is very simple to set up.

Does the TxIsoLoop-2 failsafe or provide any error signal?
In the event of an error the outputs will be zero (not 4mA), so you can distinguish between a low-end signal and a genuine fault.

Industry Applications

  • Signal Splitting for Upgrades — feeds one 4-20mA signal to two control systems during hardware transitions.
  • Ground Loop Elimination — dual independent isolators protect signal accuracy on installations with electric potential differences.
  • Asset Replacement Projects — lets old and new control systems read the same input during commissioning.