Sales & Technical Support: Mon–Fri 09:00–17:00 +44 (0)1824 520565
Novus DigiRail Connect Universal Ethernet IO Expansion Modules (Modbus, RS485) - additional product photo

Novus DigiRail Connect RAMIX | Ethernet IO Module Modbus TCP/RTU (2AI / 2AO / 4DI / 3DO)

Verkäufer
Novus
Normaler Preis
£230.00 (Exc. VAT)
Sonderpreis
£230.00 (Exc. VAT)
Normaler Preis
(Exc. VAT)
Ausverkauft
Einzelpreis
pro 

MPN: 8811611420

Delivery: Factory Order, Delivered In 7-14 Days

The Novus DigiRail Connect RAMIX 2AI / 2AO / 4DI / 3DO (8811611420) combines 2 isolated universal analogue inputs, 2 isolated analogue outputs, 4 digital inputs and 3 PNP digital outputs in one DIN rail module. The analogue inputs read thermocouples, Pt100/Pt1000, NTC and mV, V or mA signals directly at 16-bit resolution, so sensors wire straight in without separate transmitters. The outputs provide 0-20mA, 4-20mA or 0-10V for drives, valves and displays.

Every DigiRail Connect model has Ethernet, RS485 and Micro USB on board. It works as a Modbus RTU slave on an existing RS485 network or as a Modbus TCP server on Ethernet, and can act as a transparent Modbus TCP to RTU gateway, so an Ethernet PLC or SCADA system can read RS485 instruments wired to its terminals with no register mapping. Configuration and I/O testing use free Novus NXperience software over USB.

Lead time: made to order by Novus, typically 1–2 weeks to dispatch.

DigiRail Connect Range

All four DigiRail Connect models share the same Ethernet/RS485 hardware and software. Choose by the I/O mix you need:

Only need analogue inputs on RS485? The lower-cost Novus DigiRail-2A converts two thermocouple, Pt100, mV, V or mA signals to Modbus RTU.

✅ 3 Year Manufacturer Warranty — backed by our UK-based technical support

PDFNovus DigiRail Connect Datasheet Download

PDFNovus DigiRail Connect Manual Download

Technical Details

Order code: 8811611420 (DigiRail Connect RAMIX 2AI / 2AO / 4DI / 3DO ETH)

Analogue inputs: 2, isolated, universal: thermocouple J, K, T, N, E, R, S, B; Pt100, Pt1000, NTC; 0-60mV, 0-5V, 0-10V, 0-20mA, 4-20mA. 16-bit resolution

Analogue outputs: 2, isolated, 0-20mA, 4-20mA or 0-10V. 12-bit resolution

Digital inputs: 4, PNP, NPN or dry contact, configurable counter function

Digital outputs: 3, PNP transistor, 200mA max load per output, 6-30 Vdc switching

Communication: Ethernet 10/100 Mb/s (IEEE 802.3u), RS485, Micro USB

Protocols: Modbus TCP server, Modbus RTU slave, transparent Modbus TCP to RTU gateway

Configuration software: Novus NXperience (free, via USB)

Power supply: 10-36 Vdc, 5W max (20mA typical)

Operating conditions: -20 to 60°C, 5-95% RH non-condensing

Enclosure: ABS+PC, 35mm DIN rail mounting

Frequently Asked Questions

What can the analogue inputs read directly?
Thermocouples (J, K, T, N, E, R, S, B), Pt100, Pt1000 and NTC sensors, plus 0-60mV, 0-5V, 0-10V, 0-20mA and 4-20mA signals. Each channel is configured independently in NXperience.

Do I need RAMIX or DMIX?
Choose RAMIX when you need analogue measurement or an analogue output. DMIX models suit applications where every signal is on/off and you need more discrete channels.

Should I choose this 3DO model or the 2 Relay RAMIX?
This model has 3 PNP transistor outputs (up to 200mA) for PLC-level DC signals and pulsing. The 2 Relay version gives volt-free contacts for switching AC loads.

Can it provide a speed reference to an inverter?
Yes. The 0-10V or 4-20mA analogue outputs can set inverter speed, valve position or a remote display, driven from SCADA or a PLC over Modbus.

Industry Applications

  • Process monitoring — brings temperatures, pressures and flows into SCADA without separate transmitters.
  • Remote analogue control — sends speed references to inverter drives and positions proportional valves.
  • Energy & utilities — data acquisition in pump stations and plant rooms over Ethernet or RS485.