Motor Protection And Isolation For 4.00-6.30A Motors In One DIN Module
The EMAS MKS1TM-6.3 is a DIN rail manual motor protection switch (MPCB) for motors with a full load current between 4.00A and 6.30A, a popular band for workshop machinery, larger pumps, fans and conveyor drives. It combines adjustable thermal overload, fixed magnetic short-circuit and phase-loss protection, and gives you a local on/off isolator in the same compact unit.
MPN MKS1TM-6.3
- Adjustable thermal overload - set the dial to the motor's nameplate current anywhere from 4.00A to 6.30A
- Fixed magnetic trip at 12 x Ie - clears short circuits instantly, with a breaking capacity of at least 6kA at 400V
- Phase deficiency protection - trips if a 3-phase motor loses a phase
- Ambient temperature compensated - the trip point stays consistent as panel temperature changes
Technical Details
Frequently Asked Questions
How is this different from a normal MCB?
An MCB protects the cable with a fixed trip curve. The MKS1TM-6.3 protects the motor itself: its thermal trip is set to the motor's running current, it rides through starting inrush, and it adds phase-loss protection that an MCB does not have.
How do I choose and set the right range?
Read the full load current from the motor nameplate. If it falls between 4.00A and 6.30A, this is the right switch; set the dial to that value. Below 4.00A use the MKS1TM-4; from 6.30A to 10.0A use the MKS1TM-10.
Can it be mounted outside a panel?
No. The switch is rated IP40, so it should be fitted on 35mm DIN rail inside an enclosure. EMAS also make an enclosed MKS1TMK version for surface mounting; ask us if you need one.
What cable sizes does it accept?
The terminals take 0.75mm² to 4mm² conductors, tightened to 1.8Nm. Auxiliary contacts and other MKS accessories are sold separately.
Industry Applications
- Workshop machinery - overload and phase-loss protection for saws, drills and grinders with direct-on-line motors
- Pumps and fans - a combined isolator and motor protector for medium-sized pump and fan motors
- Conveyor drives - trips on jams or sustained overload before the motor windings overheat
Need a different range? See the EMAS MKS1TM-4 (2.50-4.00A) or the EMAS MKS1TM-10 (6.30-10.0A).