13A 3-Pole Contactor With 230V AC Coil And 1 N.O. Auxiliary
The EMAS HN1310NUE is a 3 pole HN series contactor with a 230V AC coil and one normally open (N.O.) auxiliary contact, for DIN rail or panel mounting. It switches three-phase motors up to 6kW at 400V (13A AC3) and resistive heating loads up to 20A (AC1). The built-in N.O. auxiliary is ideal for a run or feedback signal back to a PLC or indicator.
A common replacement for Crompton, Schneider, Telemecanique, ABB and similar contactors. Other HN sizes: 9A, 13A, 17A and 25A.
MPN HN1310NUE
- 13A AC3 / 6kW motor rating at 380-415V
- 20A AC1 thermal rating for heaters and resistive loads
- 230V AC coil, 50-60Hz, runs directly from UK mains control circuits
- Auxiliary: 1 N.O. built in
- 10 million mechanical operations, 1 million electrical (EMAS data)
EMAS HN1310NUE Datasheet Download
Technical Details
| Product | Contactor |
| Current (Ie) | 13A (AC3), 20A (AC1) |
| Motor Rating | 6kW at 380-415V, 3.2kW at 220-240V |
| Poles | 3 |
| Auxiliary | 1NO |
| Coil Voltage | 220-230V AC 50-60Hz |
| Mechanical Life | 10,000,000 operations |
| Electrical Life | 1,000,000 operations |
| Operating Frequency (On-Off/Hour) | Mech. 1800, Elec. 600 |
| Insulation Voltage (Ui) | 690V AC |
| Impulse Withstand Voltage (Uimp) | 6 kV |
| Dielectric Strength | 1890V AC |
| Isolation Resistance | 10 MΩ (500V DC) |
| Operating Temperature | -15 / +80 °C |
| Pollution Degree | 3 |
| Protection Degree | IP20 |
| Cable Section | 1,5 mm² |
| Screw Torque | 1,8 Nm |
| Short Circuit Breaking Capacity (Ics) | 50 kA |
| Standard | TS EN 60947-4-1 |
| Series | HN Series |
Frequently Asked Questions
What is the difference between AC1 and AC3 ratings?
AC1 applies to resistive loads such as heating elements and gives the higher rating (20A). AC3 applies to inductive loads such as three-phase motors and is lower (13A / 6kW at 400V) because motor inrush current is harder on the contacts.
Will the 230V coil work on UK 240V mains?
Yes. UK mains is nominally 230V, often measured at around 240V, which is within the coil's normal operating tolerance.
Is there a version with the other auxiliary contact?
Yes. The HN1301NUE is the 1 N.C. auxiliary version of this contactor. Use N.O. for a run or feedback signal and N.C. for interlocking or fault indication.
Can this replace my existing branded contactor?
Likely yes. It is a common form-factor replacement for Crompton, Schneider, Telemecanique, ABB and similar contactors. Check that the coil voltage, load rating and auxiliary contacts match before ordering.
Can it be used outdoors or in a washdown area?
No. It is IP20 and must be mounted inside an enclosed control panel.
Industry Applications
- Ovens, kilns & heaters — switching heating elements up to 20A from a temperature controller relay or SSR output
- Motor control panels — starters for pumps, fans, compressors and conveyors up to 6kW
- Panel refurbishment — drop-in replacement for ageing or discontinued branded contactors
Troubleshooting & Guides
- Kiln Temperature Control — how contactors fit into a kiln control circuit
- Kiln Controller Upgrade Parts — choosing the controller, SSR or contactor for an upgrade
- Faultfinding — diagnosing a contactor that will not pull in or chatters
- Knowledge Base — all our technical guides in one place